WNS Oil and Gas Fired Hot Water Boiler

WNS Oil and Gas Fired Hot Water Boiler

Boiler capacity:0.35MW~29MW

Pressure:0.7Mpa/1.0Mpa/1.25Mpa/1.6Mpa

Fuel:natural gas/oil/lpg/city gas

Certificate:CE,ISO:9001,SGS

 

Overview
 
 
Advantage
1,Real time monitoring of water level: Equipped with water level electronic detector to
control the water level.
2,Setting time function: The users can set the starting and stopping time as their demand.
3,Water shortage protection: When the boiler is lack of water, the system will turn off burner at the same time, electric controller will alarm.
4,Over pressure protection: When the pressure of boiler is over your setting value, burner will stop working and alarm.
5,Interlock protection:The pressure controller, water level alarms, safety valves, low water level alarm and multiple safety protection. 
WNSOiland Gas1
 
Specifications

Item

WNS0.7-0.7/95/70-Y(Q)

WNS1.4-0.7/95/70-Y(Q)

WNS2.8-1.0/95/70-Y(Q)

WNS4.2-1.0/95/70-Y(Q)

WNS7.0-1.0/95/70-Y(Q)

WNS10.5-1.25/115/70-Y(Q)

WNS14-1.25/115/70-Y(Q)

Power

MW

0.7

1.4

2.8

4.2

7

10.5

14

Working pressure

Mpa

0.7

0.7

1

1

1

1.25

1.25

Supply water temperature

95

95

95

95

95

115

115

Return water temperature

70

70

70

70

70

70

70

Circulating water amount

T/H

24

48

96

144

240

200

267

boiler body heating area

M2

28.6

57.63

107.16

197.61

291.33

427.15

517.2

rated exhaust smoke temperature

156.43

164.7

158.27

156.71

100

133.2

140.93

Design efficiency

%

90.63

90.4

90.6

90.8

94.2

93.47

93.12

Boiler weight

T

6.8

8.5

11.6

16.6

21.5

46.4

59.3

Boiler water capacity

T

3.6

4.9

9.3

12.1

15.3

31.2

39.6

Boiler with full water capacity

T

10.4

13.4

20.9

28.7

36.8

77.6

98.9

Gas consumption

NM3/H

85.6

172.8

321.2

498

631.5

1094.5

1598.5

Size

L(mm)

4440

4520

4800

5400

6750

7420

7965

W (mm)

2400

2800

3100

3100

2480

3340

3730

H(mm)

2200

2200

3050

3320

3410

3510